On January 15, 2025, Saudi General Directorate of Civil Defense (GCD) released Fire Safety Specifications for High-rise and Super High-rise Building Elevators, implemented on July 1, 2025. Core requirements:

1. Scope: All elevators in high-rise and super high-rise buildings with height ≥100 meters;

2. Fire-resistant structure: Shaft, machine room, car fire resistance ≥2 hours, door system fire resistance ≥1.5 hours, Class A fireproof materials;

3. Smoke prevention design: Shaft positive pressure air supply, automatic shutdown when smoke concentration exceeds standard, smoke-proof seal;

4. Fire operation: Automatically return to first floor in fire, open door and cut off power, special operation for firefighters, emergency lighting ≥90 minutes;

5. Emergency power supply: Independent fire emergency power supply, maintain 3 hours fire operation, automatic switch;

6. Material flame retardant: Elevator materials flame retardant V-0 grade, low smoke zero halogen, non-toxic combustion;

7. Old renovation: Existing high-rise elevators complete fire upgrade by 2028, non-compliant elevators stopped;