SH-ARD-TPS Blackout Emergency Power Supply Device
Three-phase emergency power family for the manufacturer-listed Monarch/STEP application, with model-specific battery strings and common inverter data kept separate from unsupported children.
Product Reference
manufacturer Model Matrix
| Model | Capacity | DC voltage | Battery string | Match status |
|---|---|---|---|---|
| TPS-10 | 11 kW | 36 VDC | 12 V / 7 Ah × 3 | available; product main agrees |
| TPS-11 | 15 kW | 48 VDC | 12 V / 7 Ah × 4 | available; product model option agrees |
| TPS-15 | 18 kW | 60 VDC | 12 V / 7 Ah × 5 | available; product model option agrees |
| TPS-25 | 22 kW | 72 VDC | 12 V / 7 Ah × 6 | available; product model option agrees |
| TPS-30 | 30 kW | 84 VDC | 12 V / 7 Ah × 7 | manufacturer shows 30 kW; product model option says ≤25 kW, not released as agreed data |
Common manufacturer Performance
| Parameter | Value |
|---|---|
| AC input | 380 / 415 VAC, ±20%, three phase; 50/60 Hz ±10% |
| Charger type | Controlled rectifier CVCC |
| Charge time | 10 hours for 90% full battery capacity |
| Inverter technology | IGBT-based PWM sine wave |
| Output voltage | 380 / 415 VAC, three phase; 50/60 Hz ±0.1 Hz |
| Efficiency | 85% |
| Continuous overload | 105% |
| Harmonic distortion | <3% on linear load |
| Crest factor | 4:1 |
| Power factor | 0.8 |
| Phase displacement | 120° ±1° |
| Brake-voltage options | 60 / 110 / 220 VDC |
Original Parameter Tables
Selection Questions
Which manufacturer variants are released as matching product data?
TPS-10, TPS-11, TPS-15 and TPS-25 have matching manufacturer and product capacity rows. TPS-30 remains isolated because the manufacturer shows 30 kW while the product row shows 25 kW.
Can the TPS table be applied to 220 V, single-phase or two-phase children?
No. This sheet is for the manufacturer-listed 380/415 V three-phase family. Other voltage and phase children need their own technical manufacturer.
What must be selected for an order?
Confirm motor power, input supply, required DC bus/battery string, brake voltage and the target controller interface.